SC825 CHASSISSeries SC825TQ-R720LPB SC825TQ-R740LPBSC825TQ-710LP SC825TQ-R720UBSC825TQ-R700LP(V)(B) SC825TQ-R700U(V)(B)SC825TQ-600LPB SC
SC825 Chassis Manual1-21-3 Chassis FeaturesThe SC825 2U, high-performance chassis includes the following features:CPUThe SC825 chassis supports a dua
1-3Chapter 1: Introduction Contacting SupermicroHeadquartersAddress: Super Micro Computer, Inc.980 Rock Ave.San Jose, CA 95131 U.S.A.Tel: +1 (408)
SC825 Chassis Manual1-41-5 Returning Merchandise for ServiceA receipt or copy of your invoice marked with the date of purchase is required be-fore an
2-1Chapter 2: Warning Statements for AC SystemsChapter 2 Standardized Warning Statements for AC Systems2-1 About Standardized Warning StatementsThe
2-2xxx Chassis User's ManualWarnung WICHTIGE SICHERHEITSHINWEISEDieses Warnsymbol bedeutet Gefahr. Sie benden sich in einer Situation, di
2-3Warning Statements for AC Systems안전을 위한 주의사항경고!이 경고 기호는 위험이 있음을 알려 줍니다. 작업자의 신체에 부상을 야기 할 수 있는 상태에 있게 됩니다. 모든 장비에 대한 작업을 수행하기 전에 전기회로와 관련된 위험요소들을 확
2-4xxx Chassis User's ManualInstallation Instructions Warning!Read the installation instructions before connecting the system to the power source
2-5Chapter 2: Warning Statements for AC SystemsCircuit Breaker Warning!This product relies on the building's installation for short-circuit (over
2-6xxx Chassis User's ManualPower Disconnection Warning 電源切断の警告システムコンポーネントの取り付けまたは取り外しのために、シャーシー内部にアクセスするには、システムの電源はすべてのソースから切断され、電源コードは電源モジュールから
2-7Chapter 2: Warning Statements for AC Systems¡Advertencia! El sistema debe ser disconnected de todas las fuentes de energía y del cable eléctrico qu
SC825 Chassis ManualiiManual Revision 2.0 Release Date: June 13, 2013The information in this User’s Manual has been carefully reviewed and is be
2-8xxx Chassis User's ManualEquipment Installation機器の設置トレーニングを受け認定された人だけがこの装置の設置、交換、またはサービスを許可されています。 Warning!Only trained and qualied personnel
2-9Chapter 2: Warning Statements for AC Systemsアクセス制限区域このユニットは、アクセス制限区域に設置されることを想定しています。アクセス制限区域は、特別なツール、鍵と錠前、その他のセキュリティの手段を用いてのみ出入りが可能です。 Warning!Thi
2-10xxx Chassis User's ManualBattery Handling Warning!There is the danger of explosion if the battery is replaced incorrectly. Replace the batter
2-11Chapter 2: Warning Statements for AC SystemsWarnung Bei Einsetzen einer falschen Batterie besteht Explosionsgefahr. Ersetzen Sie die Batterie nur
2-12xxx Chassis User's ManualWarnung Dieses Gerät kann mehr als eine Stromzufuhr haben. Um sicherzustellen, dass der Einheit kein trom zugeführt
2-13Chapter 2: Warning Statements for AC SystemsBackplane Voltageバックプレーンの電圧システムの稼働中は危険な電圧または電力が、バックプレーン上にかかっています。修理する際には注意ください。警告当系统正在进行时,背板上有很危险的电压或能
2-14xxx Chassis User's ManualComply with Local and National Electrical Codes Warning!Installation of the equipment must comply with local and nat
2-15Chapter 2: Warning Statements for AC SystemsProduct Disposal Warning!Ultimate disposal of this product should be handled according to all national
2-16xxx Chassis User's ManualWaarschuwing De uiteindelijke verwijdering van dit product dient te geschieden in overeenstemming met alle nationale
2-17Chapter 2: Warning Statements for AC SystemsWarnungDie Lüfter drehen sich u. U. noch, wenn die Lüfterbaugruppe aus dem Chassis genommen wird. Halt
iiiPrefacePrefaceAbout This ManualThis manual is written for professional system integrators and PC technicians. It provides information for the insta
2-18xxx Chassis User's Manual Warning!When installing the product, use the provided or designated connection cables, power cables and AC adaptors
2-19Chapter 2: Warning Statements for AC SystemsAttention Lors de l'installation du produit, utilisez les bables de connection fournis ou désigné
2-20xxx Chassis User's ManualNotes
3-1Chapter 3: Chassis ComponentsChapter 3 Chassis Components3-1 OverviewThis chapter describes the most common components included with your chassis
SC825 Chassis Manual3-2Power SupplyEach SC825 chassis model includes a high-efciency power supply rated at 560W (single), 563W (single) 600W (single)
4-1Chapter 4: System InterfaceChapter 4 System Interface4-1 OverviewThere are LEDs on the control panel and the drive carriers to keep you constantl
SC825 Chassis Manual4-2•Power Failure: When this LED ashes, it indicates a power failure in the power supply.•Overheat/Fan Fail: When this LED
4-3Chapter 4: System Interface•Power: Indicates power is being supplied to the system's power supply units. This LED should normally be illumina
SC825 Chassis Manual4-44-4 Drive Carrier LEDsYour chassis uses SAS/SATA or SCSI drives, but not both. SAS/SATA DrivesEach SAS/SATA drive carrier has
5-1Chapter 5: Chassis Setup and MaintenanceChapter 5 Chassis Setup and Maintenance5-1 OverviewThis chapter covers the steps required to install comp
SC825 Chassis ManualivManual OrganizationChapter 1 IntroductionThe rst chapter provides a checklist of the main components included with
SC825 Chassis Manual5-25-3 Removing the Chassis CoverRemoving the Chassis Cover1. Remove the two screws on each side of the cover, which secure the
5-3Chapter 5: Chassis Setup and Maintenance5-4 Installing Hard DrivesRemoving Hard Drive Trays from the Chassis1. Press the release button on the dr
SC825 Chassis Manual5-4The drives are mounted in drive carriers to simplify their installation and removal from the chassis. These carriers also
5-5Chapter 5: Chassis Setup and Maintenance3. Install a new drive into the carrier with the printed circuit board side facing down so that the mounti
SC825 Chassis Manual5-65-5 Installing an Optional Floppy or Fixed Hard DriveThe SC825 chassis models include two open slots for an optional
5-7Chapter 5: Chassis Setup and Maintenance5-6 DVD-ROM Replacement or InstallationMost SC825 chassis models include a DVD-ROM which is usually pre-in
SC825 Chassis Manual5-85-7 Installing the MotherboardI/O ShieldThe I/O shield holds the motherboard ports in place. Install the I/O shield before you
5-9Chapter 5: Chassis Setup and MaintenancePermanent and Optional StandoffsStandoffs prevent short circuits by securing space between the motherboard
SC825 Chassis Manual5-10Installing the Motherboard1. Review the documentation that came with your motherboard. Become familiar with component placeme
5-11Chapter 5: Chassis Setup and MaintenanceAdd-on Card/Expansion Slot SetupSC825: chassis include I/O slots for add-on cards and expansion cards. The
vPrefaceAppendicesThis section lists compatible cables, power supply specications, and compatible backplanes. Not all compatible backplanes ma
SC825 Chassis Manual5-12Add-on Card/Expansion Slot Setup for SC825U (Universal Output)SC825U chassis accepts a slightly smaller "L" shaped m
5-13Chapter 5: Chassis Setup and Maintenance5-8 Installing the Air ShroudAir shrouds concentrate airow to maximize fan efciency. The SC825 chassis
SC825 Chassis Manual5-14Checking the Server's Air FlowChecking the Air Flow1. Make sure there are no objects to obstruct airow in and out of th
5-15Chapter 5: Chassis Setup and MaintenanceThree heavy duty fans provide cooling for the chassis. These fans circulate air through the chassis as a m
SC825 Chassis Manual5-16Figure 5-15: Placing the System Fan
5-17Chapter 5: Chassis Setup and MaintenanceDepending on your chassis model, the SC825 Chassis has a 560, 600, 700, 710, 720 or 740 Watt power supply
SC825 Chassis Manual5-18Replacing the Power Supply1. If your chassis includes a redundant power supply (at least two power mod-ules), you can leave t
5-19Chapter 5: Chassis Setup and MaintenanceReplacing the Power DistributorRedundant server chassis that are 2U or greater require a power distributor
SC825 Chassis Manual5-20Replacing or Installing the Front Port PanelReplace or Install the Front Port Panel1. Power down and unplug the system2. Remov
5-21Chapter 5: Chassis Setup and Maintenance5-11 Optional Front BezelThe SC825 chassis supports an optional full-face locking front bezel for added s
SC825 Chassis ManualviTable of ContentsChapter 1 Introduction1-1 Overview ...
SC825 Chassis Manual5-22Notes
6-1Chapter 6: Rack InstallationChapter 6 Rack Installation6-1 OverviewThis chapter provides a quick setup checklist to get your chassis up and runni
SC825 Chassis Manual6-2Rack Precautions•Ensure that the leveling jacks on the bottom of the rack are fully extended to the oor with the full weight
6-3Chapter 6: Rack InstallationRack Mounting ConsiderationsAmbient Operating TemperatureIf installed in a closed or multi-unit rack assembly, the ambi
SC825 Chassis Manual6-46-4 Rack Mounting InstructionsThis section provides information on installing the SC825 chassis into a rack unit with the quic
6-5Chapter 6: Rack InstallationFigure 6-2: Installing the Inner Rail ExtensionsInstalling the Inner Rail ExtensionThe SC825 chassis includes a set of
SC825 Chassis Manual6-6Outer Rack RailsOuter rails attach to the rack and hold the chassis in place. The outer rails for the SC825 chassis extend betw
6-7Chapter 6: Rack Installationscrew the handles the outer rails for secure purpose if necessaryF.ABLECOMDATE:2008/08/14REV:2SCREWSCREWCOMPLETE12Figur
SC825 Chassis Manual6-8Notes
B-1Appendix B: Power Supply Specications Appendix B SC825PowerSupplySpecicationsThis appendix lists power supply specications for your chassis
viiPrefaceAir Shroud ... 3-23-3 Where to get Repl
SC825 Chassis ManualB-2SC825 Series710W DC-DC Power SupplyR720W (Redundant)740WMFR Part # PWS-711-1R PWS-721P-1R PWS-741P-1RRated AC Voltage------100-
A-1Appendix A: Chassis CablesAppendix A SC825 Chassis CablesA-1 OverviewThis appendix lists supported cables for your chassis system. It only inclu
SC825 Chassis ManualA-2SC825TQ-R700LP Part # Type Length DescriptionCBL-0157L Ribbon 9"8 pin to 8 pin ribbon cable for SGPIO, PB freeCBL-0087Ribb
A-3Appendix A: Chassis CablesA-4 CablesIncludedwithSC825S2Chassis(SCSI)SC825TQ-560LP Part # Type Length DescriptionCBL-0157L Ribbon 9"8 pin
SC825 Chassis ManualA-4A-5 Compatible CablesThese cables are compatible with the SC825 Chassis.Alternate SAS/SATA CablesSome compatible motherboards
A-5Appendix A: Chassis CablesExtending Power CablesAlthough Supermicro chassis are designed to be efcient and cost-effective, some compatible motherb
SC825 Chassis ManualA-6Notes
C-1Appendix C: BPN-SAS-825TQ Backplane SpecicationsAppendix C BPN-SAS-825TQBackplaneSpecicationsTo avoid personal injury and property damage, c
C-2SC825 Chassis ManualC-3 An Important Note to UsersAll images and layouts shown in this user's guide are based upon the latest PCB Revision av
C-3Appendix C: BPN-SAS-825TQ Backplane Specications11163248BAR CODEREV 2.0SAS825TQ1GNDGND+12V +5VGNDGND+12V +5V#2I C#1ACT_INJP29:9072 RESETI CSIDEBAN
SC825 Chassis ManualviiiChoosing a Setup Location ... 6-1Rack Precautions ..
C-4SC825 Chassis ManualBackplaneMain Power4-Pin ConnectorPin# Denition 1+12V2 and 3 Ground4 +5VCD-ROM/FDD Power4-Pin ConnectorPin#
C-5Appendix C: BPN-SAS-825TQ Backplane Specications#8 and #9 Sideband HeadersThe sideband headers are designated JP51 and JP52. For SES-2 to work pro
C-6SC825 Chassis Manual11163248BAR CODEREV 2.0SAS825TQ1GNDGND+12V +5VGNDGND+12V +5V#2I C#1ACT_INJP29:9072 RESETI CSIDEBAND #2SIDEBAND #122++++++++++++
C-7Appendix C: BPN-SAS-825TQ Backplane SpecicationsSGPIO and I2C Modes and Jumper SettingsThis backplane can utilize SGPIO or I2C, which is the defau
C-8SC825 Chassis ManualI2CSettings(Default)Jumper Jumper Setting NotesJP33 2-3 Controller ID #1JP34 1-2Backplane ID #11-2: ID#02-3: ID#1JP36 2-3 Co
C-9Appendix C: BPN-SAS-825TQ Backplane SpecicationsSAS Port Connections in I2C and SGPIO Settings Use the following chart when connecting this backpl
C-10SC825 Chassis ManualR156R155D8D7D6D5D26D23D20D19D25D22D21D18D15D14D13D12C106++++++++++++++++FAIL1ACT0FAIL0ACT2FAIL2ACT1FAIL4ACT3FAIL3ACT5FAIL5ACT4
C-11Appendix C: BPN-SAS-825TQ Backplane SpecicationsNotes
C-12SC825 Chassis ManualDisclaimer (cont.)The products sold by Supermicro are not intended for and will not be used in life sup-port systems, medical
Chapter 1 Introduction1-1 OverviewSupermicro’s SC825 2U chassis features a unique and highly-optimized design. The chassis is equipped with high ef